Air Conditioning Pipe

30 11 2009

A central air conditioning and ventilating system has an exterior air intake duct and a plurality of dampers for opening and closing air ducts. One damper is positioned in the exterior air intake duct and a second damper is positioned in the interior of a return air duct and a third damper is positioned in the interior return air duct escape air duct. The first damper can be opened while the second damper is closed and a third damper opened to convert the air conditioning system to a whole house ventilation system.

For more HVAC Supply, visit bidformaterials.com for more questions and other refernces.





Slow Pace Of HVAC Change Means Missed Gains

21 11 2009

Energy technologies used in buildings have advanced rapidly over the past decade. Although no wholly new HVAC technologies have appeared in that period, many options have improved, become more reliable or dropped in cost. Still, many HVAC technologies that could cut operating costs, such as variable-speed drives and energy management systems, remain underused.

With an understanding that what’s new for one customer may be old hat to another, here’s a brief shopping list of options.

More Efficient Central Cooling Systems

Electric chillers — complete with variable-speed drives, oversized heat exchangers, hot gas bypass control, to name a few features — have redefined efficiency from a “good” .7 kw/ton in 1990 down to about .5 kw/ton or better, cutting power demand and consumption almost 30 percent. Gas-fired reciprocating or double-effect absorption cycle chillers replace demand for electricity with use of natural gas. Thermal storage systems have become modular and more reliable, allowing them to fit into spaces with only marginal real estate value. Where electricity is expensive year-round, “free” cooling using cooling tower condenser water is no longer uncommon.

Rooftop and packaged units containing compressors and fans have become significantly more efficient, mostly as a result of changes to product efficiency standards mandated by the 1992 federal Energy Policy Act. Improvements of 20 to 30 percent are now common. Heat pumps and window air conditioning units are 10 to 15 percent better than they were only a decade ago.

Better HVAC Distribution Options

Those same federal standards raised minimum efficiencies for fan and pump motors and now require variable-speed drives on smaller units. VAV fans down to 30 horsepower must now be able to run efficiently at lower loads.

Although not necessarily designed purely for energy efficiency purposes, underfloor air distribution and radiant cooling systems, as well as dedicated outside air systems, are becoming more accepted as their reliability improves and their installation costs drop.

Economizer cycles, which replace return air with outside air when it is cooler, and air-to-air heat exchangers, sometimes called displacement systems, have been around for decades, but are now required by code for many new air system designs.

More Controls Clout

A variety of sophisticated control systems are also either required or accepted to meet building codes for new construction. A good list can be found in the changes made between ASHRAE’s 90.1-1989 standard and its 90.1-1999 version, which is now part of the federal standard that all states are supposed to adopt as part of their own building codes by mid-2004. Among those options to meet code are:

  • Automatic ventilation controls for high-occupancy areas, including variable outside air volume based on carbon dioxide monitoring.
  • Zone and loop controllers incorporating control error correction, plus a deadband when separate thermostats control heating and cooling in a zone; doing so limits reheating and recooling done by separate systems.
  • Automatic shutoff controls for the supply of conditioned air, outside air and exhaust air to each zone, as well as automatic shutdown controls for off-hour operations or only minimal flow to maintain temperature.
  • Motorized dampers in stair and elevator shafts and outdoor air supply exhaust hoods, vents and ventilators to minimize updrafts and infiltration.
  • Resettable chilled and hot water temperatures in smaller systems —over 300,000 Btuh instead of the previous 600,000 Btuh.

  • Potential Savings

Although savings will vary greatly depending on climate, energy pricing, and building type and age, analyses by the U.S. Department of Energy indicate that applying just the relevant HVAC aspects of the 1999 ASHRAE code to America’s stock of buildings could yield savings of about 2 percent on electric usage, almost 3 percent on gas, and about 2 percent on overall energy bills, relative to present consumption. Comparing that to pre-1989 code buildings as a base, another 2 to 3 percent — for a total of about 5 percent — could be taken off annual energy bills for all U.S. non-residential buildings.

At first blush, that may not seem like a lot, but those numbers are based on the total building stock in the United States. A simplified calculation for a 160,000-square-foot office park in a mid-Atlantic climate finds its energy and dollar savings ranging from 8 to 15 percent, relative to the same facility being built before the 1989 standard came into play. In rough dollars, that boils down to about 15 to 35 cents per square foot per year, roughly comparable to many high-efficiency lighting upgrades.

Despite the range of choices, their proven track records and the potential savings, there has been no rush to take advantage of the newer technologies and designs. Why? There are several reasons.

One is that taking on any new technology involves a learning curve and some risk of failure or inconvenience. In the absence of an in-house champion for energy cost cutting, there may be no one to make the case that upgrading HVAC systems will make much financial difference.

Experience also shows that, for every one person willing to say “yes” to energy efficiency, there are 10 who say “no.” The first items to be value engineered out of a building’s mechanical design, for example, are often energy efficiency options that are not needed to make the overall system work acceptably.

In one major Northeastern institution, building operators resisted changing out their single-stage absorption chillers, fed by expensive utility steam, for a hybrid electric and gas-fired absorber plant because of a lack of knowledge and training on the new system.

In another case, word-of-mouth stories about how some new technologies were problematic or did not deliver expected savings were enough to block consideration of newer versions that had acceptable track records.

Many dyed-in-the-wool HVAC practitioners show little interest in learning about new technologies. Such technical inertia may stem from an attitude that says all hours of personnel time should be allocated to an existing job, so only a request from a customer to consider a new option will result in an investigation. An increasingly litigious culture also creates a financial risk when specifying, designing or installing anything not already tried-and-true.

Problems may also occur during adjustment of a base building design to accept new devices that, to be more efficient, are larger than originally called for or are unavailable in sizes needed to accommodate existing or projected needs. One customer wanted to install exhaust air heat exchangers in a lab building, but doing so would have required changing the setback on the floor containing the air handlers, which would have disrupted the building’s appearance.

Many new systems involve longer lead times for delivery that are unacceptable in tight building construction schedules. If a device is not readily available, whatever is on the shelf at the local supply house may be installed instead.

The incrementally higher cost of some new systems — including design, installation and commissioning — may also stand out more than potential savings, which typically take years to cover. Any possibility of selling the building during that time period creates uncertainty about recouping those extra costs.

For existing buildings, installing a new system may require alteration or contact with other systems or spaces that could create new problems. High-efficiency motors, for example, may require replacement of old circuit breakers unable to accommodate their higher in-rush current. If those power panels are touched, that may require upgrading them to meet new electrical codes, resulting in disruption and higher costs.

Some complex options, such as cogeneration, are very sensitive to changes in utility rates, thus creating significant financial risk for developers and building owners. Such fears lead to a wait-and-see attitude that is often the kiss of death.

Finally, the method to calculate savings from such new devices may be outdated or too narrow. Where average power pricing is used instead of a computer model that takes time-of-use costs into account, savings could appear lower than may actually occur. In other cases, savings or credits that should be taken are left off the balance sheet. When an electric chiller was to be replaced with a gas-fired unit, for example, a significant drop in a building’s peak electric demand would have resulted, allowing for installation of new power-consuming devices like a mainframe computer without a need to beef up the transformer or main electric service capacity. That large avoided cost was not included in the payback analysis for the chiller changeout, yielding an unacceptably long payback period.

No Pressing Need

Another reason that more efficient HVAC technologies haven’t been adopted more quickly is the absence of factors that make energy upgrades a higher priority within corporations. In many parts of the country, for example, energy prices were relatively stable for most of the 1990s, eliminating a major impetus for upgrading HVAC systems.

In other cases, a developer has no concern for the operating cost of the building because the occupants will pay the energy bills. Any additional cost may even make the structure harder to sell.

In roughly a third of states, energy codes either do not exist or are so poorly enforced that contractors know there is essentially no reason to comply with them. The increase in demand for fire and electric code inspections has swamped many jurisdictions, leading them to drop inspections or reviews for such non-safety issues as energy. Until the adoption of ASHRAE 90.1-1999 in 2004, most energy codes apply only to new buildings, allowing renovations, which affect the lion’s share of buildings, to escape coverage.

When most utility-sponsored energy rebates were dropped in the late 1990s as a result of power industry restructuring, many companies lost interest in pursuing the options once supported by such “free” money.You can see more of HVAC Supply at bidformaterials.com.





Heating and Ventilation

18 11 2009

Heating & Ventilation Image

Heating & Ventilation Image

Heating & Ventilation systems generally consist     of both supply and return air systems that circulate the air through a designated area.

Specifications for specific job applications.

Some examples of these abilities are:

  • General Ductwork Systems
  • Kitchen Ventilation & Canopy Systems
  • Dust and Fume Extraction – C.O.S.H.H.
  • Room Pressurisation Systems – Food & Pharmaceutical Specification
  • Marine Specifications
  • Hospital & Healthcare Specifications

Informations in HVAC Supply, you can visit bidformaterials.com to know all about heating and ventilation.





Strategies for HVAC Systems

10 11 2009

Heating and air-conditioning systems account for 50-80 percent of the total energy use in most commercial and institutional buildings. With such a high percentage of energy use concentrated in these two areas, it is no surprise that the recent rise in energy prices and concerns over energy supplier reliability have prompted maintenance and engineering managers to focus attention on these systems, particularly boilers and chillers.Even a slight improvement in the operating efficiency of these components translates into big cuts in energy use and costs. Suppose the average load on a large chiller plant is 3,000 tons. If a manager can improve its average operating efficiency from 0.91 kW/ton to 0.70 kW/ton, the monthly savings will top $27,000, assuming an average electricity cost of $0.06 per kWh.

While managers can take many steps to improve the operating efficiency of chillers and boilers, all energy-improvement programs should start by making existing equipment operate as efficiently as possible.

How can technicians achieve this goal? Two steps can enhance operation – monitoring and maintenance. Basic maintenance, such as cleaning and adjustments, will keep boilers and chillers operating so they minimize energy use.

But the only way to achieve peak operating efficiencies is to regularly monitor operating parameters. Data from a monitoring program will tell operators how to adjust the equipment and will identify the need for maintenance tasks.

Chiller Monitoring

Chillers present a challenge to managers when it comes to operating efficiency. While manufacturers rate chiller efficiency at full load, most building chillers rarely operate at full load. Part-load efficiencies are lower and vary with a number of parameters, including supply and return chilled-water temperatures, entering condenser-water temperature, and condenser and chilled-water flow rates.

Compounding the challenge is the level of precision needed in measuring each parameter to calculate efficiency accurately. An error of as little as 1 degree in water-temperature measurements can cause an error in the efficiency calculation of 1-2 percent. A similar error in flow measurement can result in an even larger error in calculating efficiency. Therefore, it is critical to install high-quality flow meters and temperature sensors and to maintain them properly.

To be effective, a chiller efficiency-monitoring program must be ongoing. As data is collected under different operating conditions, managers will develop an efficiency performance baseline for the chiller. Technicians should compare this baseline to the manufacturer’s published performance curve to determine if the chiller is performing as efficiently as possible.

As data continues to be compiled, technicians will be able to monitor trends in performance. While managers can expect a slight deterioration in performance, due to normal wear and tear, they should look for trends that might indicate a need for maintenance, such as cleaning the chiller’s tubes, a replacing refrigerant, or overhauling the chiller.

Fortunately, a new generation of monitoring equipment is available to assist managers in monitoring chiller performance. This equipment collects the necessary data and automatically calculates the chiller’s efficiency.

The equipment then compares the operating parameters and the calculated efficiency to past performance values, triggering an alarm if a value falls outside the expected range. By constantly monitoring chiller operation, the systems assist in keeping chillers at peak operating efficiency, and they help technicians detect and troubleshoot problems.

Boilers

Efficiency calculations for chillers determine overall efficiency expressed as the ratio of energy input to energy output. Boilers require a different efficiency calculation – combustion efficiency.

A boiler’s combustion efficiency measures how completely fuel burns and how effectively the generated heat transfers to water or steam. The measurement does not take into account heat loss from the boiler’s surface, blowdown loss, or energy used by auxiliary equipment. With good test equipment, technicians can measure it with 98 percent accuracy or greater.

Managers have two reasons for using the combustion test instead of an overall efficiency test. First, it is practically impossible to measure all necessary parameters accurately, including the energy content of the fuel. More importantly, boiler losses excluded from the combustion efficiency calculation remain relatively constant. While technicians need to check them periodically, they do not require ongoing monitoring.

Combustion-efficiency testing is one of the most accurate means of adjusting a boiler and its auxiliary equipment for both safe and efficient operation. To do so, technicians can install a portable unit temporarily on a boiler for testing or permanently for ongoing monitoring.

Technicians most often use oxygen sensors to test a boiler’s combustion efficiency. The equipment uses an electronic sensor in the boiler’s flue that measures oxygen in the flue gas. Changes in combustion efficiency, such as those caused by varying levels of excess air, show up as varying levels of oxygen in the flue gas.

For small boilers, technicians most often use a portable combustion-efficiency tester setup at the beginning of every heating season. By adjusting the boiler each year, managers can achieve higher levels of operating efficiency in multiple small boilers without making a significant investment in equipment.

Medium-sized boilers can use the same setup, but technicians can achieve greater efficiency by testing the boiler at least monthly during the heating season. For larger boilers, it is most effective to permanently install the equipment and connect it to the boiler’s control system. In this configuration, technicians can use the equipment to adjust the boiler under all heating loads to achieve the most efficient operation.

Pumps

Managers often overlook pumps when looking for ways to improve HVAC system operating efficiency. As a result, inefficient pump operation can go uncorrected for the life of the system. And with most HVAC system pumps operating when the system operates, inefficiency can result in large amounts of lost energy.

Perhaps the most important factor when installing pumps is that specifiers must match them to the system’s requirements. As the flow rate increases or decreases from the design point of the pump, the efficiency of the pump decreases. So it is important that managers select a pump based on the system’s required flow rate and the pressure exerted on the pumping system. If the system must operate over a range of flow rates, a variable-speed pump system provides the best operating efficiency.

Once in operation, technicians should periodically test pumps for proper flow rate and pressure differential. And they should plot readings against the manufacturer’s pump curve to determine if the pump is operating within its specified range.

Take a visit to choose HVAC Supply for more choices for maintenance tasks based on needs.





HVAC Maintenance and Energy Savings

9 11 2009

In spite of years of studies, demonstration programs, and published stories to the contrary, most facility organizations today still operate in a reactive mode. Though facility executives know that is far better to schedule maintenance activities using planned and predictive maintenance tools, most continue to spend the bulk of their resources operating reactively. The most common reasons cited for this is the lack of sufficient resources.

This approach to maintenance with respect to HVAC systems is particularly troubling given the role that HVAC systems play in today’s facilities. HVAC systems in typical commercial buildings are responsible for more than 40 percent of total energy use. Keeping HVAC supply system running properly and at peak efficiency is the first step in managing facility energy use.

The importance of good HVAC system maintenance goes beyond just controlling energy use. Buildings today depend on properly operating systems for more than just people comfort. For example, most telecommunications systems have requirements for specific environmental conditions to operate properly. Temperatures and humidity levels that fall outside of this range can lead to interruption in services and even costly system failures. Sometimes the difference between keeping a business running and having to shut down is nothing more than proper HVAC system maintenance.

What Goes Wrong

In spite of all the supporting data and facility executives’ efforts, most organizations underfund maintenance. Reactive maintenance remains the norm, not the exception. Maintenance is deferred. Planned and predictive maintenance remain the exception. The most commonly cited reason for not performing routine and preventive maintenance on HVAC equipment is lack of resources. The C-suite rarely has facility experience and does not fully understand the need for maintenance. To many who establish and control budgets, maintenance is an overhead cost. Like other overhead costs, steps should be taken to reduce it. Reducing overhead costs increases profit margins. And like other overhead costs, the only impact of this reduction is reduced costs. Proper maintenance of HVAC systems requires careful planning and forward thinking, both of which become lost when maintenance is considered nothing more than an overhead expense.

Contributing to this belief is the unfortunate fact that HVAC systems are not the most noticeable components in a facility. Unlike highly visible items, such as carpet or lighting systems, most HVAC systems are out of sight and out of mind, until something goes wrong. And when something does go wrong, it is too late for maintenance to be performed efficiently. Maintenance at that point becomes reactive.

Reactive maintenance is the most costly way to maintain building HVAC systems. Organizations that have implemented comprehensive planned and predictive maintenance programs show dramatic decreases in maintenance costs. And when factors are included, such as extended equipment life, reduced energy use, less frequent system downtime, and decreased interruptions to building operations, organizations that have implemented comprehensive maintenance programs find that their total costs can be as much as 50 percent lower than the costs for those organizations that continue maintain equipment reactively.

While it is easy to blame those who control the budget, facility executives themselves are at least partially to blame. If facility executives are to receive the budgetary support necessary to carry out their mission, they must present their case in the terms that are best understood by budget managers. Simply saying that money is needed to overhaul or replace a chiller, particularly when the chiller is still running, is not enough. Facility executives should be able to demonstrate the consequences of ignoring HVAC system maintenance while identifying the real cost savings associated with comprehensive maintenance. Demonstrate that dollars spent on the maintenance of these systems will result in an improvement in the bottom line.

Location, location, location. The phrase is a real estate cliché. In maintenance budgeting, the key is documentation, documentation, documentation. Funds in organizations, particularly during economic downturns, are limited. Competition for those funds is intense. Other departments have pet projects that they are promoting. They are the competition. If facility executives want to level the playing field, they should make the case that investing money in HVAC maintenance will provide the organization a rate of return that is equal to or even greater than what others are promoting. And that requires documentation.

Properly maintaining HVAC systems provides a number of benefits that facility executives readily understand. Proper documentation of these benefits will help budget managers develop the same level of understanding.

Energy Savings

One of the easiest benefits to document is how HVAC maintenance affects energy efficiency. Facilities in which proper HVAC maintenance is completed will use at least 15 to 20 percent less energy than those where systems are allowed to deteriorate.

For example, consider the operation of a central building chiller. Building chillers typically are the single largest user of electricity in a facility. To keep them operating as efficiently as possible, maintenance tasks must be performed on a daily, weekly, monthly and annual basis. Let them lapse, and efficiency will decrease, increasing energy use.

Start with the chiller operating log. Work with the chiller manufacturer or a service company to translate the log data into an operating efficiency curve for the chiller. Develop a similar curve for what the efficiency of the chiller would be if all maintenance were performed at the recommended intervals. The difference between the two operating efficiencies can be translated into energy and cost savings. Due to the high energy use of the equipment, even small increases in efficiency will result in large savings.

While the energy savings estimates for chillers, boilers, and many other HVAC systems is straightforward, others savings estimates may not be. Consider outside air dampers. Air dampers require regular maintenance to respond properly to the temperature control system’s demand for ventilation air. If the damper linkage is out of adjustment, or if it sticks open, more ventilation air will be introduced than necessary, requiring the system to use more heating or cooling energy to condition that air.

Regular inspection, testing and maintenance of the damper will keep it operating properly, minimizing energy use. Document what needs to be done, how much it will cost, and what the cost would be for a stuck damper. Show how much a stuck open damper would cost in terms of energy use.





Cooling and Air Conditioning Equipment

5 11 2009

All air cooled chillers are mounted in a steel superstructure, epoxy painted and the condenser coils are protected with a diamond mesh screen.

Air ChillerMultiple containerized chillers are used for large projects – 1000 + tons are constructed using a number of 500 ton chillers built up with custom manifolds, providing redundancy and a high level of reliability. Additional equipment can be added or maintenance can be performed with minimal or no downtime.

 

Cooling Tower All cooling towers are mounted on a skids and range in sizes from 500 to 750 tons. Many meet class 1, div. 2, Group C & D ratings.

 

 

 

Our air conditioners are available from 5 to 120 tons and room spot coolers from 1 to 5 tons. Uncontrolled temperature and moisture levels can often have a devastating effect on equipment life and air quality. Our air conditioners are available from 5 to 120 tons and room spot coolers from 1 to 5 tons. Our 40 and 80 ton units meet class 1, div. 2, group C & D explosion proof rating. Every air conditioner is a unique unit design specifically by Carrier Rental Systems.Spot Cooler.

Our desiccant dehumidifiers, produce up to 4500 cfm. Our desiccant dehumidifiers, produce up to 9000 cfm. To deliver total comfort during the dehumidification process, we also provide fridge-drying packages up to 88,000 cfm.

 

 

 

For more HVAC Supply, visit bidformaterials.com for further information.

 





HVAC HAND TOOLS

3 11 2009

HVAC Driver

Klein Tools Basic Insulated Hand Tool Kit

Klein Tools High-Leverage 8 3/4 Inch Side-Cutting Pliers

Klein Tools Screwdriver Set w/ Mini Cushion-Grip Handles – 4 Pieces

There will always have a good source of hand tools and  there are example of  HVAC Supply at bidformaterials.com.





Parts for HVAC Contractors

28 10 2009

TEST EQUIPMENT

Bacharach
Refrigerant recovery equipment, Test instruments to detect, measure and record combustion and environmental gases, temperature, relative humidity, air velocity, and other air quality and safety parameters.

Reftec
Refrigerant Handling Equipment: Refrigerant Recovery, Noncondensible Gas Purging, Chiller Pressurization, Refrigerant Management

Ritchie Yellow Jacket®
Yellow Jacket® Refrigerant Recovery Systems, Vacuum Systems, Test Instruments, Vacuum and Charging Hoses and Specialized Gauges

SPX Service Solutions (Robinair, TIF and Promax)
Refrigerant Recovery Systems, Vacuum Systems, Test Instruments, Gauges and Hoses

Fieldpiece
Hand-held test instruments for installation, maintenance and repair: Stick-Style Meters, Clamp-On Meters, Superheat and Subcooling Tools, Thermometers and Standalone Instruments

Fluke
Test and measurement instruments: Digital Multimeters, Electrical Testers, Clamp Meters, Meg Ohm Meters, Thermometers and IAQ Tools

Dwyer
Precisions instruments for measuring, transmitting and controlling pressure, temperature, level and flow.

 

HVAC Supply for a great and convenient use .





Experienced HVAC

26 10 2009

The P.I.P.E. Union recruitment video – Upgrade you life as a Union HVAC/R Repair Tech. The Union provides great benefits that include medical, savings and pentions plans as well as free high tech training.

After making your decision about HVAC training. Kindly visit HVAC Supply at bidformaterials.com.





HVAC Return Air Ducting

22 10 2009

HVAC Return Air Ducting
Air Conditioning Sizing – Tips on Ductwork

There is nothing more uncomfortable than lying in bed on a hot summer night sweating. Tossing and turning does no good. What’s worse, you know that the first floor or basement of your house is much more comfortable. Does it have to be this way? Absolutely, positively NOT!

My house and lots of others that I have built and remodeled are very comfortable, even in the hottest weather. The reason is simple. My HVAC contractor, Richard Anderson, knows the importance of return air ducting AND sizing correctly both supply and return air ducts. This is the key to comfort.

Existing Hot Houses

I’ll bet that 3 out of 5 people who read this bulletin have an existing home that has no or inadequate return air ducts. Don’t worry, we are going to solve those problems. It isn’t always going to be easy or pretty, but it can be done.

Return air ducts are necessary in just about every room. However, there are two rooms that I never place return air ducts – kitchens and baths. Let’s try to keep the garlic odors and hair spray in these rooms if you don’t mind! The reason for return air is simple. Your furnace is simply a recirculating pump. Instead of pumping water, it is pumping air. We need to get the air back to the pump. Furthermore, without a return air duct in each major room, the supply duct air has to “push” all of the air in the room out of the way as it makes its way towards you. The return air ducts help pull the air as it is being pushed.

Where Can You Put Them?

If you have an existing ranch style home, installing return air ducts in each room can be done fairly easily. You do what we do in new homes. You use the wall cavities as the duct. Think of it. Drywall that is nailed to 2×4s is really a duct – a box with 4 sides. All you have to do is cut out the floor immediately below the wall cavity as well as the bottom wall plate. Once you have created the opening, sheet metal will allow you to connect this to your existing return air system.

Two story houses can be more of a challenge. You have to figure out a way to get return air from the ceilings of the second floor to the basement or furnace room.

Do you have a laundry chute that you don’t use that often? Can it be sacrificed for the cooling cause? We have used these with tremendous success.

Sometimes, you can use a kitchen pantry closet or a hall closet. We have often been able to put a duct in one corner of the pantry or closet. This duct extends up to the second floor where it often lines up with an interior hallway wall.

Often you can collect the ceiling air through a network of flexible pipes in an attic. These pipes join together in one central location that permits you to run a duct down to the basement or a second floor closet.

// //

As a last resort, you may have to put a duct in the corner of a room(s). These can be drywalled easily. To effectively disguise it, you may build another one several feet down the wall. Shelves can be put between these two “stacks”. If they are in a child’s room, they can often be painted in a decorative manner as if it was intended for them to be there.

It was common in many older homes to have projections in rooms such as this. These bump outs often were fireplace chimneys as they rose through to the roof.

Balancing Return Air Flow

If you want to really have a way to get the most bang for your return air buck, think of installing grill covers on the wall that have operating louvers. This will allow you to choke down rooms possibly on the first floor that are drawing too much air. This in turn creates a greater suction in the rooms that really need the cool air. This principle is no different than dampers which are used on supply lines to regulate air flow.

The grills with louvers are inexpensive and effective. On an older existing home that is being retrofitted for central air-conditioning, they are a must.

Reversed Air Flow On Old Homes

Do you have a house that is approximately 80 years old? If so, your supply ducts may be on inside walls. You may have a single giant return air grill in the floor or at the bottom of a staircase. This is all wrong.

Supply ducts should be located on outside walls, preferably under windows and near doors. The intent is to wash the exterior walls with heated or cooled air. You are trying to combat the heat or cold at its source.

The single giant return air grill in the floor balances the load at the furnace motor, but does nothing to promote cross ventilation in each room.

I wish you luck in your effort to stay cool in good HVAC Supply.